| Property | Flat with roof terrace above a ground-floor hair salon |
|---|---|
| Location | Shepherd’s Bush, London W12 |
| Survey | Thermal imaging survey with roof moisture testing and flood testing |
| Client | Homeowner |
The problem
For more than ten years, water had been coming through the ceiling of the hair salon below this flat, mostly during and after heavy rain. The roof terrace had been repaired several times, most recently about two months before our visit, when an extra layer of asphalt was laid over the old one. The leak carried on, and the contractors said it must be coming from somewhere else.
What our surveyor found
- The staircase below the terrace was wet. Readings were significantly elevated, so water was still getting in, not just old staining.
- Water ponded on the roof. A controlled bucket flood test showed water standing instead of draining away. Standing water sits on every joint and crack for hours, so small defects become leaks.
- The roof was wet under the new layer. Roof moisture testing showed elevated readings across sections of the asphalt. Overlaying a wet, poorly falling roof can trap moisture and even worsen ponding.
- Cracked render and open joints at the parapet. Small cracks in the parapet render, gaps at the flashings, and weathered coping stones with open joints all give wind-driven rain a way in.
Our conclusion
The leak is rain-driven, which points to the building envelope, not plumbing. There isn’t one hole: ponding on a roof with poor falls, plus defective parapet render, coping joints and flashing junctions, together explain a leak that’s lasted a decade. Adding more asphalt treats the symptom and can make the falls worse.
What we recommended
- Stop overlaying. Open up the affected roof section to check the condition of the build-up and how much moisture is trapped, and correct the falls to the outlet.
- Repair or replace defective coping stones and renew open joints, so the parapet head is weathertight.
- Cut out cracked render back to sound material and properly weather the render, flashing and upstand junctions. Don’t just run sealant over them.
- Dry, then re-test the staircase and ceilings before replastering or decorating.
The takeaway
If a roof keeps leaking after repairs, the repair has probably treated the wrong thing. A survey that tests the roof, the parapet and the drainage together finds the real route in before more money goes on another layer.