| Property | Edwardian solid-wall building split into two flats |
|---|---|
| Location | Dartford, DA1 |
| Survey | Damp and mould survey |
| Client | Landlord |
The problem
A leak from the upper flat had caused damp on the walls and ceiling of the flat below. The landlord asked us to investigate both flats, find the cause and set out what needed doing.
What our surveyor found
- The leak came from the shower tray fittings in the upper flat. It had been contained, but the walls below were slow to dry, so they stayed damp, lost heat and attracted mould.
- Gaps behind the bathroom tiles. Thermal imaging showed cold spots on the ceiling and open joints in the wall tiles, letting water vapour build up behind them and trickle down.
- A weak extractor fan. Measured with an anemometer, the bathroom fan moved about 10 litres per second, below the 15 l/s recommended in Part F of the Building Regulations.
- High humidity: around 70–75% in the hall and bathroom, well above the 40–60% range in BS 5250.
- Mould in a bedroom, where the external wall had become moisture-laden.
Our conclusion
The leak started the problem, but poor ventilation and high humidity kept it going. Both needed fixing, or the mould would keep coming back after the leak was repaired.
What we recommended
- Maintain the shower pipe fittings, reseal the gaps with waterproof mastic and regrout with a waterproof grout.
- Fit a humidistat extractor fan that meets the Part F flow rate.
- Add positive input ventilation or a passive vent to the affected bedroom.
- Treat the mould with a fungicidal wash once the source and ventilation are sorted.
The takeaway
For landlords, fixing the leak is only half the job. Measuring humidity and fan performance gives you evidence of what’s needed, which matters when tenants report damp and mould.
We carry out independent damp surveys in Dartford and across north-west Kent.
Landlord dealing with damp or mould between flats? A mould and condensation survey gives you a clear, evidence-based report. Get a free quote.